    Three-Phase Motor Power Calculator

    P = √3 · V · I · cosφ · η. Use this to size cables, breakers and VSDs.

    Inputs
    Result
    Apparent power
    13.86 kVA
    Active (shaft) power
    10.84 kW
    Shaft power
    14.53 hp

    Notes & assumptions

    • For VSD-driven motors derate efficiency by 1–3% to account for inverter losses.
    • Confirm cosφ at operating load — nameplate is typically the 4/4 full-load value.